Penerapan Sistem Synchron CBE (Close Before Excitations ) Pada Diesel Generator Konvensional

Author


Mohammad Suharto(1Mail), Iwa Garniwa Mulyana K(2),
(1) Institut Teknologi PLN Jakarta, Indonesia,
(2) Institut Teknologi PLN Jakarta, Indonesia,

Mail Corresponding Author
Article Analytic
  [File Size: 961KB]  Language: en
Available online: 2026-02-20  |  Published : 2026-02-20
Copyright (c) 2026 Mohammad Suharto, Iwa Garniwa Mulyana K
Article can trace at:

Article Metrics

Abstract Views: 25 times PDF Downloaded: 9 times

Abstract


This article analyzes the performance of generator set (genset) synchronization systems using the Dead Bus Close Before Excitation (CBE) method compared to the live bus method, and evaluates the dynamic response of gensets through block load testing, PID tuning, and burning tests. The test results show that the Dead Bus CBE synchronization method achieves an average synchronization time of approximately 9 seconds, faster than the live bus method, which requires about 18 seconds, resulting in a time efficiency improvement of 50%. This improvement directly impacts the reliability of the backup power system and reduces dependence on Uninterruptible Power Supply (UPS) battery capacity. Block load testing shows that the genset can handle 050% load with stable voltage and frequency responses, meeting the requirements of ISO 8528-5. In the 0100% block load test, a voltage drop of up to 19% and a frequency decrease of 9% were observed, with a recovery time of approximately 5.5 seconds, classified as a conditional pass according to the standard. PID tuning results on the Digital Automatic Voltage Regulator (DAVR) and governor were proven to improve transient response, reduce voltage drop magnitude, and enhance system stability during synchronization and sudden load acceptance. Additionally, the burning test results indicate that the genset can operate continuously under high load with stable voltage, frequency, and thermal parameters without triggering protection faults. Overall, this study demonstrates that implementing Dead Bus CBE synchronization supported by proper PID tuning can improve the response speed, stability, and reliability of gensets as backup power sources for critical loads.

Keywords


Generator Set; Dead Bus Synchronization; Close Before Excitation (CBE); Digital Automatic Voltage Regulator (DAVR); PID Tuning

References


[1] Alt?nkaya, H. and Ekmekci, D. (2024) Tuning of PID Controller in PLC-Based Automatic Voltage Regulator System Using Adaptive Artificial Bee ColonyFuzzy Logic Algorithm, Electronics (Switzerland), 13(24).

Mahmoud, R.A. and Elwakil, E.S. (2025) Out-of-step detection for synchronous generators using electrical power analysis and Durbin Watson testing, Scientific Reports, 15(1), pp. 133.

Gozdowiak, A. and Antal, M. (2025) A Synchronization of Permanent Magnet Synchronous Generator Dedicated for Small and Medium Hydroelectric Plants, Energies, 18(8).

Prasetyo, D.B. and Kiswantono, A. (2021) Sinkronisasi Dan Monitoring Generator Dengan Pengendali Berbasis Arduino Mega 2560, Aisyah Journal of Informatics and Electrical Engineering, 3(2), pp. 163170.

Mahtani, K., Guerrero, J.M. and Platero, C.A. (2024) Improved Instantaneous Current Value-Based Protection Methods for Faulty Synchronizations of Synchronous Generators, Electronics (Switzerland), 13(23).

[Woodward, Option K27 - Run-up Synchronization, manual 37454b

[Deni Hendarto, J.S. (2014) Penerapan Metode Dead Bus Untuk Sinkronisasi Genset Cadangan, provaided by Electronic Journals of UIKA Bogor, pp. 813.

Antono, D. and Khambali, M. (2013) Penerapan Sinkronisasi Jaringan Listrik Tiga Fasa PLN dengan Generator Sinkron Menggunakan Trainer Power Sistem Simulation, Jtet, 2(3), pp. 151158.

Thompson, M.J., Ravikumar, K.G. and Laboratories, S.E. (2011) New Developments in Generator Synchronizing Systems, Sel, pp. 19.

[10] Warman, E. (2021) Sinkronisasi Generator 635 Kva Dengan Generator 635 Kva Menggunakan Module Deep Sea, Jurnal Simetri Rekayasa, 5035, pp. 187195.

Scientific Report.Out - of- step detections for sychronouse generator using electrical power analysis and durbin watson testing 2025 15:20113

Suid, M.H. et al. (2024) AVR System Improvement: Fast and Optimal Tuning PID Control Using Safe Experimentation Dynamics Algorithm, 2024 International Conference on System Science and Engineering, ICSSE 2024, pp.

[29] Mahmoud, R. A. & Malik, O. P. Out-of-step detection of synchronous generators using dual computational techniques based on correlation and instantaneous powers. IET Gener. Trans. Distrib. 16, 27162746 (2022).

[30] S. Chatterjee and V. Mukherjee, PID controller for automatic voltage regulator using teaching-learning based optimization technique, Int. J. Electr. Power Energy Syst., vol. 77, pp. 418 429, 2016

[31] Z. L. Gaing, A particle swarm optimization approach for optimum design of PID controller in AVR system, IEEE Trans. Energy Convers., vol. 19, no. 2, pp. 384391, Jun. 2004.

[32] H. Gozde, Robust 2DOF state-feedback PI-controller based on meta-heuristic optimization for automatic voltage regulation system, ISA Trans., vol. 98, pp. 2636, Mar. 2020


Refbacks

  • There are currently no refbacks.

Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.